Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU01667
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2010 | FIRE - ALARM FINAL | Approved | Approved 6/29/10 | |
05/20/2010 | FIRE - ALARM FINAL | Denied | 1. RELABEL FLOORS ON PLANS PG. FA2 & FA3 2. ADD PLENUM FIRE DAMPTERS ON 2ND LEVEL TO ALARM SYSTEM DAMPERS STAYED CLOSED AT ALL TIMES EVER OPENED BACK UP. PG. FA2 3. LOWER LEVEL FLOOR ADD PULL STATION AND SMOKE IN HALLWAY NOT SHOWN ON PLAN. 4. REDRAW PLAN SHOWING MISSING HALLWAY. PG. FA3 |