Permit: T09BU01629

Parcel: 116190740


Addresses:

233 N MAIN AV


Inspection Status: Approved

Inspection History: POOL/SPA PLUMBING

Permit Number - T09BU01629

Inspection Description - POOL/SPA PLUMBING

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2009 POOL/SPA PLUMBING Approved IVRS - Inspection :*
12/03/2009 POOL/SPA PLUMBING Not ready for Inspection IVRS - Inspection :*
12/01/2009 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*
1) PLAN ON SITE HAS NO CITY STAMP, ATMOSPHERIC RELIEF REQUIRED ON DRAIN LINE
2) IF NON-METALLIC CONDUIT USED FOR WET NICHE FIXTURE A CU. STRANDED #8 WIRE REQUIRED FROM FIXTURE CAN (EPOXY COATING ON CONNECTION BACK TO INSULATED J-BOX
3) PLEASE LEAVE LISTING GOR LIGHT FIXTURE
4) NOTE: SEE NOTES REF MOTOR CONTROLLER AND WIRING 5' FROM POOL EDGE
5) ALSO ENCLOSURE/BARRIER ARE METAL CLOSER THAN 5'-0" TO POOL EDGE NEEDS TO BE BONDED BACK TO MOTOR
6) NEED TEMP BARRIER AROUND POOL ASAP
7) 25 PSI H20 ON LINES
11/25/2009 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*
1) OK TO BACK FILL POOL ONLY
2) PROVIDE AIR TEST ALL ?
11/04/2009 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*
1) OK TO BURY 1 1/2" LINES AT BEND ONLY
2) KEEP JOINTS EXPOSED
3) NOT UNDER TEST AT THIS TIME