Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09BU01609

Parcel: 10712225A


Addresses:

2835 N STONE AV #07


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T09BU01609

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2009 FIRE SPKLR - OH PIPING & HYDRO Approved 225 PSI TEST FOR 2 HOURS APPROVED
ADD SPRINKLER COVERAGE IN THE FOLLOWING AREAS;
LUNDRY ROOM ABOVE DRYERS
UNDER STAIRWELL
CLOSET WHERE FOLDING WALLS ARE STORED
NEED AS-BUILT PLANS FOR CHANGES