Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09BU01606
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2009 | MECHANICAL - FINAL | Approved | ||
10/29/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MVA INLET TO CLOSE TO WASTE VENTS. PROVIDE 10' HORIZONTAL OR 3' VERTICAL ON WASTE VENTS 2) PROVIDE HINGE KITS ON KITCHEN EXHAUST, REMOVE SCREWS AND PROVIDE GASKET BETWEEN FAN AND DUCT TERMINATION 3) KITCHEN EXHAUST ELECTRICAL ROOF JACK NOT PROPERLY INSTALLED 4) LOW VOLTAGE CONTROL WIRING NOT PROPERLY INSTALLED 5) PROVIDE SERVICE OUTLET WITHIN 25' OF SERVICEABLE EQUIPMENT 6) PROVIDE BACK WALL ON HOOD, THIS HOOD IS DESIGNED AS A WALL UNIT, NOT AS AN ISLAND FAN 7) PROVIDE BACK WALL ON HOOD, THIS HOOD IS DESIGNED AS A WALL UNIT, NOT AS AN ISLAND FAN 8) PROVIDE HEAT SENSOR INTERLOCK TEST AMD E.F./MVA INTERLOCK TEST 9) PROVIDE KITCHEN BALANCE REPORT 10) NEED TO VERIFY DUCT WRAP AND SMOKE TEST FOR LEAKAGE |