Permit: T09BU01606

Parcel: 117121280


Addresses:

135 E CONGRESS ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09BU01606

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2009 MECHANICAL - FINAL Approved
10/29/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MVA INLET TO CLOSE TO WASTE VENTS. PROVIDE 10' HORIZONTAL OR 3' VERTICAL ON WASTE VENTS
2) PROVIDE HINGE KITS ON KITCHEN EXHAUST, REMOVE SCREWS AND PROVIDE GASKET BETWEEN FAN AND DUCT TERMINATION
3) KITCHEN EXHAUST ELECTRICAL ROOF JACK NOT PROPERLY INSTALLED
4) LOW VOLTAGE CONTROL WIRING NOT PROPERLY INSTALLED
5) PROVIDE SERVICE OUTLET WITHIN 25' OF SERVICEABLE EQUIPMENT
6) PROVIDE BACK WALL ON HOOD, THIS HOOD IS DESIGNED AS A WALL UNIT, NOT AS AN ISLAND FAN
7) PROVIDE BACK WALL ON HOOD, THIS HOOD IS DESIGNED AS A WALL UNIT, NOT AS AN ISLAND FAN
8) PROVIDE HEAT SENSOR INTERLOCK TEST AMD E.F./MVA INTERLOCK TEST
9) PROVIDE KITCHEN BALANCE REPORT
10) NEED TO VERIFY DUCT WRAP AND SMOKE TEST FOR LEAKAGE