Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09BU01558
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FIRE SUPPERSION FINAL |
|
02/19/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
02/12/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT WRAP ON TYPE I GREASE DUCT MUST BE INSPECTED PRIOR TO INSTALLATION 2) ITEM 4 DATED 10/21/09 |
|
01/14/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) WELD ON GREASE DUCT DROPS OK 2) OK TO WRAP DUCT (2 AT3') |
|
10/28/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) KITCHEN HOOD OK 2) ALL OTHER ITEMS FROM PREVIOUS INSPECTION MUST BE CORRECTED |
|
10/21/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL GREASE DUCTS CONNECTED TO HOOD AND TO FAN ON ROOF DO NOT MEET TYPE I REQUIREMENTS 2) ALL GREASE DUCTS AND RELATED PLENIUMS AND CLEANOUTS MUST BE 16 GA. WELDED DUCTS 3) EXHAUST FAN NEEDS THE REQUIRED HINGE KIT AND A GREASE RECEPTOR AND GASKET UNDER FAN 4) MAKE UP AIR MUST BE INTERLOCKED WITH THE EXHAUST FAN 5) THE HOOD DOES NOT MEET TYPE I REQUIREMENTS 6) JOINTS AND SEAMS ARE POP RIVETED 7) THE TOP OF THE HOOD IS GALVANIZED SHEET METAL ATTACHED WITH SCREWS 8) GREASE DUCTS ARE NOT WELDED TO HOOD |