Permit: T09BU01544

Parcel: 12810082B

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
10/30/2009 FIRE - KITCHEN EXH HOOD FINAL Approved Approved 10/30/ 09.
10/20/2009 FIRE - KITCHEN EXH HOOD FINAL Denied 1.) Need detectors over each appliance.
2.) The make-up air did not shut off upon activating the system.
3.) Need a "K" type extinguisher for the kitchen area.