Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/03/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE APPROVED QUIK DSICONNECT HOSE AND LEASH ON ALL APPLIANCES WITH WHEELS 2) SEAL ALL HOLES IN EXTERIOR OF WOOD AND WALL FLASHING 3) PROVIDE SMOKE CONTAINMENT TEST 4) COMPLETE ITEM 2 DATED 8/28/09 ALL OTHER ITEMS COMPLETE |
|
| 08/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IT APPEARS THAT THE GREASE DUCT HAS A JOINT THAT IS NOT WELDED 2) SEAL THE BOTTOM OF SHAFT WITH SEET METAL 3) INTERLOCK MAKE UP AIR WITH EXHAUST FAN 4) PROVIDE A 16 GA. STEEL PLATE AT TOP OF DUCT AND WELDED TO DUCT 5) PROVIDE A HINGE KIT FOR EXHAUST FAN 6) PROVIDE A GREASE RECEPTOR AT FAN 7) PROVIDE A GASKET BETWEEN FAN AND CURB |