Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/22/2009 | FIRE SPKLR - FINAL | Approved | ||
| 09/24/2009 | FIRE SPKLR - FINAL | Denied | 1.) The upper two sprinkler heads added to this area are obstructed by the trusses. 2.) Must submit a revised set of plans. This can be done under the initial permit. A new permit is not required. |
|
| 09/02/2009 | FIRE SPKLR - FINAL | Partial Approval | All four sprinkler heads that were added must be accessable for inspection. |