Permit: T09BU01098

Parcel: 11712017A


Addresses:

55 N 6TH AV

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/10/2009 FIRE - ALARM FINAL Approved
08/04/2009 FIRE - ALARM FINAL Denied 1. FACP AND NAC'S need to be on dedicated circuits.
2. Need lock outs on each breaker.
3. On each door to NAC'S and FACP label where the electical panel is located and breaker number.
4. Label each battery when it was installed.