Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09BU01087
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
10/05/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE PROPER DRAIN ON EXHAUST FAN 2) PROVIDE GASKET ON EXHAUST FAN 3) SINGLE WALL PIPE VENTING ON WATER HEATER NOT TO EXTEND THRU CEILING |
|
09/30/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROCEED AS DISCUSSED |
|
09/09/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
07/29/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL 1. PROVIDE HINGE KIT ON KITCHEN EXHAUST HOOD FAN 2. GREASE DUCT MUST BE WELDED AT DUCT TERMINATION CONTINOUSLY AND LEAK FREE 3. REPAIR ELECTRICAL CONDUCT TO EXHAUST FAN 4. HOOD SYSTEM ABOVE GAS OVEN MUST BE TYPE 1 AS ORIGINALLY INSTALLED , INCLUDING ALL DUCT/HOOD CONNECTIONS, FILTERS, FIRE SUPPRESSION SYSTEM, REEF TOP DUCTING, FANS, CURBS |