Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE 2) OK FOR FIRE SUPPRESSION SYSTEM |
|
| 09/17/2009 | MECHANICAL - FINAL | Partial Approval | CHECKED FIRE WRAP ON DUCT EXTENSION INTO CURB. OK TO PROCEED | |
| 09/16/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/11/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECKED GREASE DUCT EXTENSION ON ROOF-OK FOR BOTH LAYERS OF FIRE WRAP |
|
| 07/21/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INTERLOCK MAKE UP AIR WITH EXHAUST FAN 2) PROVIDE NON COMBUSTIBLE WALL COVERING WITHIN 18" OF HOOD 3) PROVIDE A GREASE CUP AND DRAIN FOR TROUGH AROUND HOOD AND WELD THE CORNERS OF HOOD AND CAULKING 4) PROVIDE 2 LAYERS OF FIRE WRAP ON EXPOSED DUCT IN ATTIC AND SEAL OFF BOTTOM OF EXISTING SHAFT WITH SHEET METAL 5) EXTEND GREASE DUCT TO THE TOP OF FAN CURB AND PROVIDE A SHEET METAL PLATE 6) PROVIDE A GASKET UNDER FAN AND A HINGE KIT 7) DO NOT USE AN EXTENSION CORD TO POWER THE FAN, USE APPROVED METHODS 8) PROVIDE A GREASE RECEPTOR AT FAN |