Permit: T09BU00987

Parcel: 133231390

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09BU00987

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/18/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BROKEN CONDUIT TO EXHAUST FAN WITH WIRES EXPOSED STILL HAS NOT BEEN REPLACED
11/04/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PERFORMED A CAPTURE AND CONTAINMENT TEST ON EXISTING HOOD
2) THE HOOD IS WORKING FINE
3) OK TO INSTALL AND TEST NEW ANSUL SYSTEM
4) PROVIDE A NEW CONDUIT TO EXHAUST FAN ON ROOF TO REPLACE THE BROKEN EXISTING CONDUIT
09/10/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
09/09/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/09/2009 MECHANICAL - FINAL Denied PROVIDE ACCESS TO ROOF.
THE OPENING IN THE HOOD MUST EXTEND A MINIMUM OF 6" BEYOND THE COOLING SURFACE OF THE STOVE.
07/17/2009 MECHANICAL - FINAL Denied 1) PROVIDE A GREASE RECEPTOR AT FAN ON ROOF
2) REPAIR BROKEN DISCONNECT AND CONDUITS TO FAN ON ROOF
3) THE GREASE DUCT IS OK
4) THE APPLIANCES DO NOT FIT UNDER THE HOOD AS PER SECTION 507.12 2006 I.M.C.
5) INTERLOCK WITH MAKE UP AIR IS-OK