Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T09BU00974
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2009 | POOL/SPA ELECTRIC | Approved | ||
08/05/2009 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) EXPOSED ROMEX TO BE IN CONDUIT, IF YOU WANT TO KEEP IT, FEEDS A RECEPT, MUST BE 10'-0" FROM POOL EDGE 2) NEED BOND GRID INSPECTION NEXT 3) FROM LAST INSPECTION NEED MDX PIPING DIAGRAM |
|
07/22/2009 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) CAN'T FIND HOME RUN CONDUIT 2) 2 POLE 50/50 DISCONNECT IN REAR YARD NOT ON PLAN 3) OK TO GUNITE 4) PLEASE LEAVE MDX PIPING ISOMETRIC FOR NEXT INSPECTION |