Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/07/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE ON SITE, GATES LOCKED |
|
| 07/20/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX CONNECTOR NOT APPROVED FOR TYPE I (GREASE LADEN VAPOR) APPLICATION 2) PROVIDE GREASE RECEPTOR ON ROOF UNDER EXHAUST FAN DRAIN PORT |
|
| 07/01/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) HOOD, EXHAUST FAN AND RELATED DUCT WORK ARE ALL TYPE I APPROVED 2) HOOD FILTERS ARE NOT PROPERLY INSTALLED AND WILL NOT FIT THE RIGHT WAY-PROVIDE PROPER FILTERS 3) THE FLEX CONNECTOR ON THE ROOF IS ROTTED AND IS NOT APPROVED FOR TYP I 4) PROVIDE A LISTED CONNECTOR OR WELD DUCTS TOGETHER 5) EVERYTHING ELSE IS OK |