Permit: T09BU00947

Parcel: 11628001L

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09BU00947

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2009 ELECTRIC - FINAL Approved PERMIT # FOR SERVICE EXTENSION 1335 H0000??
SEE NOTE #1 LAST INSPECTION
OK T&NT CONTR, WIRING
10/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/24/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE VERIFY PERMITS FOR NEW INSTALLED EQUIPMENT AT SERVICE
2) FINISH PANEL LABELING 408.4
07/23/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER 250.24
2) NEED CONDUCTOR ADAPTER FOR NEUTRAL TERMINATION
3) LABEL BREAKERS 408.4
SERVICE:
1) NEED MAIN BONDING JUMPERS-100 + 200 AMP DISC
2) MULTI POLE LUG TERMINATIONS AT GROUND 400 AMP DISC
3) LABEL DISCONNECTS