Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09BU00947
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2009 | ELECTRIC - FINAL | Approved | PERMIT # FOR SERVICE EXTENSION 1335 H0000?? SEE NOTE #1 LAST INSPECTION OK T&NT CONTR, WIRING |
|
10/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/24/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY PERMITS FOR NEW INSTALLED EQUIPMENT AT SERVICE 2) FINISH PANEL LABELING 408.4 |
|
07/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED GROUNDING ELECTRODE SYSTEM FOR TRANSFORMER 250.24 2) NEED CONDUCTOR ADAPTER FOR NEUTRAL TERMINATION 3) LABEL BREAKERS 408.4 SERVICE: 1) NEED MAIN BONDING JUMPERS-100 + 200 AMP DISC 2) MULTI POLE LUG TERMINATIONS AT GROUND 400 AMP DISC 3) LABEL DISCONNECTS 4) ARRANGE CABLES IN FRONT OF SERVICE FOR SAFE WORKING CONDITIONS |