Permit: T09BU00914

Parcel: 135042010

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
04/26/2012 FIRE SPKLR - OH PIPING & HYDRO Approved This permit was not closed out and therefore expired (10-23-2010), Allen fire called and asked if they can get the permit cleared out. Permit was renewed for this inspection. OH PSI test was not done; system has been under normal pressure for 14 months no leaks. The sprinkler system has been in service for during this whole time.
Placement was checked found one head in kitchen installed wrong was fixed during inspection.