Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2009 |
FIRE SPKLR - FINAL |
|
Approved |
75-72-75 2" drain test. 47 sec bell time on flow switch. |
| 07/21/2009 |
FIRE SPKLR - FINAL |
|
Cancelled |
|
| 06/26/2009 |
FIRE SPKLR - FINAL |
|
Not ready for Inspection |
Upright heads needed in new overframed roof area |