Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2009 | FIRE - ALARM FINAL | Approved | Approved 11/20/09 | |
| 11/13/2009 | FIRE - ALARM FINAL | Denied | Not approved 11/13/09 1.) Replace the Heat detector with a Smoke detector (north corridor, smoke detector # A36) 2.) Smoke detector too close to register (center hallway. detector # A26) 3.) Need to add a smoke detector between smokes # A10 and smokes #12 (south corridor) 4.) Need breaker locks. All else is approved. |