Permit: T09BU00903

Parcel: 130060010

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/20/2009 FIRE - ALARM FINAL Approved Approved 11/20/09
11/13/2009 FIRE - ALARM FINAL Denied Not approved 11/13/09
1.) Replace the Heat detector with a Smoke detector (north corridor, smoke detector # A36)
2.) Smoke detector too close to register (center hallway. detector # A26)
3.) Need to add a smoke detector between smokes # A10 and smokes #12 (south corridor)
4.) Need breaker locks.

All else is approved.