Permit: T09BU00873

Parcel: 14042075F


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
10/23/2009 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
10/20/2009 POOL/SPA ELECTRIC Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) NO PLANS ON SITE
2) NO CONTRACTOR ON SITE
3) LEAVE MESSAGE WITH CONTACT NAME AND NUMBER
10/15/2009 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK GROUNDING CONNECTION TO LIGHT FIXTURE
08/18/2009 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK BOND FOR GAS AND SCUPPERS AT COLUMNS
08/10/2009 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK EQUPOTENTIAL BOND GRID WIRE
2) OK BOND FOR RAILS AND BRASS CUPS
3) OK BONDING AT FOUNTAIN
08/06/2009 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) DENIED BY RICH UNDER 08035
2) BOND GRID CONDUCTOR TO BE 18"-24 FROM ALL EDGES FOLLOW THE CONTOURS
07/27/2009 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK CONDUIT STUB UP
2) OK BOND AT POOL JUNCTION BOX
3) CALL FOR EQUIPOTENTIAL GRID BONDING NEXT
07/24/2009 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) BOND ALL BOXES
2) FINISH STOP CONDUIT RUN
3) OK SHELL PER GUNITE OF ELECTRIC ONLY