Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2009 | FIRE - ALARM FINAL | Approved | ||
| 11/30/2009 | FIRE - ALARM FINAL | Partial Approval | TEMP C OF O APPROVED FOR TRAINING ONLY!! NO OVERNIGHT SLEEPING. 1. 1st FLOOR MOVE SMOKES IN ROOM 153 & 152 MENS & WOMENS BATHROOMS MUST BE 3 FEET AWAY FROM ALL VENTS. 2. SUITE SHOP MOVE SMOKE 3 FEET AWAY FROM ALL VENTS. 3. MECHANICAL ROOM #162 SMOKE REMOVED - PULL STATION ADDED IN FITTNESS ROOM & PULL STATION ADDED IN MAIN ELECTRICAL ROOM. NEED AS BUILTS FOR CHANGES. 4. SMOKE IN HALLWAY BY ROOM210 CAME IN AS 218 & 218 CAME IN AS 220, NEED TO CHANGE PROGRAMING. 5. ROOM #232 HORN NOT PULSING & ROOM 222 HORN DEAD. 6. ROOM 300 7 301 HORNS NOT PULSING. 7. BY ROOM 320 SMOKE MISSING NOT PER PLAN, NEED AS BUILTS. 8. NEED AS BUILTS FOR CHANGES ON ADDING AND REMOVING DEVICES AND FOR FLOOR PLAN CHANGES. 9. A/C POWER OFF AND POWER OFF TO ALL NAC'S FAILED TO SHOW AT FACP AS POWER FAILURE NEED TO CHECK ON PROGRAMING. |
|
| 11/25/2009 | FIRE - ALARM FINAL | Not ready for Inspection | NEED TO MOVE SMOKES 3 FEET AWAY FROM ALL VENTS IN MENS AND WOMENS BATHROOMS AND SUITE ROOM 1ST FLOOR 1ST FLOOR DONE WITH TESTING |