Permit: T09BU00783

Parcel: 113041500

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
08/01/2011 FIRE - KITCHEN EXH HOOD FINAL Approved
03/08/2011 FIRE - KITCHEN EXH HOOD FINAL Cancelled IVRS - RI canceled
02/28/2011 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Checked messages stated they wanted an inspection for 3:00PM Monday 28 (call number 593871-01), I was at the building from 2:45pm to 3:15 PM no one showed.
2. Need gas turned back on before doing hood final.
02/10/2011 FIRE - KITCHEN EXH HOOD FINAL Cancelled Cancelled 2/10/11
06/23/2009 FIRE - KITCHEN EXH HOOD FINAL Denied 1. Wires for shut down shall be installed outside of Ansul box.
2. No exhaust fan on hood for stove, griddle or fryer some one has removed it off the roof. Will need permit and plan to install new one.
3. Make up air fail to work this shall be interconnected when hood system is turned on make air comes on. Also make air will need to shut down if extinguisher system actives