Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09BU00735

Parcel: 122160010


Addresses:

3645 E PIMA ST


Inspection Status: Partial Approval

Inspection History: FIRE - ALARM FINAL

Permit Number - T09BU00735

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
09/09/2009 FIRE - ALARM FINAL Partial Approval Approval will be given when payment for as builts is in.
08/18/2009 FIRE - ALARM FINAL Partial Approval Replace horn in maintenance room sounder failed to work.
Room M104 strobe/horn failed to work.
Air handler #4 failed to shut down.
Reprogram tamper switches in basement section 4, now coming in as flows.
08/13/2009 FIRE - ALARM FINAL Partial Approval OK TO ALLOW SCHOOL FOLLOWING AREA NEED TO BE REPAIRED.
ZONE#3
1. Mechanical Mezzanine air fans number 4 and 6 failed to shut down, number 28-29-30.
2. Ansul's in kitchens are not hooked up to alarm system.
3. Kitchen duck detectors need to be tested with power on in building C #42 and 43.
4. In SAHBA area bathroom needs a strobe installed or remove all fixtures.
ZONE#4
1. IA area air handlers failed to shut down.
2. MP104 Health science lab - Strobe failed
3. Health office pull - station cover hard to remove
4. Chiller room horn failed by east entrance doors.
5. Tamper switch outside chiller room building (south side) sending in as flow setting off alarms need to change it as trouble.
6. Tamper switch in basement above head (north wall) came in as flow alarm need to change as trouble.
08/06/2009 FIRE - ALARM FINAL Partial Approval The follwing testing was done on areas of Page 14,15,19 on approved plans.
A/C units faled to shut down when testing duct smokes. AH-7 and AH-8 for girls and boys locker rooms.
Horns not sounding in the ROCT air force building hallway, old horns.
Horns not working in lobby of Gym.
08/04/2009 FIRE - ALARM FINAL Partial Approval The follwing testing was done on areas of Page 8,12,16 and 18 on approved plans.
NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NAC'S
Tampers failed in area "M" north first floor.
Strobe in hallway area "M" first floor next to 2-007 needs replacing.
07/02/2009 FIRE - ALARM FINAL Partial Approval The follwing testing was done on areas of Page 3,6,7 and 17 on approved plans.
NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NAC'S