Inspection Status: Partial Approval
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU00735
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2009 | FIRE - ALARM FINAL | Partial Approval | Approval will be given when payment for as builts is in. | |
08/18/2009 | FIRE - ALARM FINAL | Partial Approval | Replace horn in maintenance room sounder failed to work. Room M104 strobe/horn failed to work. Air handler #4 failed to shut down. Reprogram tamper switches in basement section 4, now coming in as flows. |
|
08/13/2009 | FIRE - ALARM FINAL | Partial Approval | OK TO ALLOW SCHOOL FOLLOWING AREA NEED TO BE REPAIRED. ZONE#3 1. Mechanical Mezzanine air fans number 4 and 6 failed to shut down, number 28-29-30. 2. Ansul's in kitchens are not hooked up to alarm system. 3. Kitchen duck detectors need to be tested with power on in building C #42 and 43. 4. In SAHBA area bathroom needs a strobe installed or remove all fixtures. ZONE#4 1. IA area air handlers failed to shut down. 2. MP104 Health science lab - Strobe failed 3. Health office pull - station cover hard to remove 4. Chiller room horn failed by east entrance doors. 5. Tamper switch outside chiller room building (south side) sending in as flow setting off alarms need to change it as trouble. 6. Tamper switch in basement above head (north wall) came in as flow alarm need to change as trouble. |
|
08/06/2009 | FIRE - ALARM FINAL | Partial Approval | The follwing testing was done on areas of Page 14,15,19 on approved plans. A/C units faled to shut down when testing duct smokes. AH-7 and AH-8 for girls and boys locker rooms. Horns not sounding in the ROCT air force building hallway, old horns. Horns not working in lobby of Gym. |
|
08/04/2009 | FIRE - ALARM FINAL | Partial Approval | The follwing testing was done on areas of Page 8,12,16 and 18 on approved plans. NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NAC'S Tampers failed in area "M" north first floor. Strobe in hallway area "M" first floor next to 2-007 needs replacing. |
|
07/02/2009 | FIRE - ALARM FINAL | Partial Approval | The follwing testing was done on areas of Page 3,6,7 and 17 on approved plans. NEED LOCK OUTS ON BREAKERS FOR ALARM PANEL AND NAC'S |