Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2009 | FIRE - ALARM FINAL | Approved | ||
| 12/24/2009 | FIRE - ALARM FINAL | Denied | 1. BOOSTERS NOT WORKING ON BATTERY BACK UP. 2. 3RD FLOOR HANDI-CAPS FAILED 3. 2ND FLOOR PULL STATION NORTH END FAILED. |
|
| 12/23/2009 | FIRE - ALARM FINAL | Denied | 1st floor done all smokes and sounders 2nd floor smoke in hallway done - sounders in room did not work wiring cut. 2nd floor 2 handi-cap rooms did not sound alarms in room but did send notification to FACP 3rd floor no horns or strobes 3rd floor open loop |