Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T09BU00691
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2009 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
07/09/2009 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Need as builts. 2. Pull station is block from proper operations 3. Duct work wrong on plans, states 15"X15" when actual is 18" X 48". Plan shows using 2W nozzle when actual is 1W and 2W nozzles. 4. Salamander plumb wrong plan shows 2 - 1/2N nozzles, actual is 1 - 1N. 5. Hood nozzles on plan show on end and middle, actual both nozzles in the middle on a tee. 6. Adjust all nozzles to hit there proper aiming points on appliances not the back wall. 7. Gas failed to shut down when system was tested. |