Permit: T09BU00634

Parcel: 14118530B


Addresses:

9538 E OLD VAIL RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09BU00634

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/30/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO HAVE SEAL OFF AT BOUNDARY
2. HAVE UNCLASSIFIED WIRING IN CLASS 1 DIV 2 AREA
3. DISCONNECTING MEANS AND EMERGENCY SHUT OFF TO MEET REQUIREMENTS OF NEC 514.11 & 514.13
4. INSTALL PER NEC 514
5. RECALL WHEN READY