Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CLEARLY MARK DISCONNECTING MEANS FOR PROPANE DISPENSER 2. NEED DISCONNECTING MEANS TO MEET NEC 514.11 NEEDS TO DISCONNECT GROUNDED (NEUTRAL) CONDUCTOR 3. FINISH WORK AND RECALL |