Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T09BU00413
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2009 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
04/21/2009 | FIRE - KITCHEN EXH HOOD FINAL | Denied | IFC 904.3.5 SHALL HAVE HOOD SYSTEM TIED INTO THE FIRE ALARM SO WHEN HOOD SYSTEM ACTVATES ALARM WILL SOUND. NFPA 96 MAKE UP SHALL SHUT DOWN WHEN EXTINGUSHER SYSTEM ACTVATES. SHALL WIRE SYSTEM TO HAVE MAKE UP AIR SHUT DOWN WHEN SYSTEM ACTVATES. |