Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BUSHING AT TOP END OF CUT OFF RIGID CONDUIT BOND BUSHING 514.16-501.30 2. SOUTH DISPENSER SEAL OFF NOT POURED 3. USE APPROVED SEAL OFF FITTING AT TOP OF DISPENSER PER 514.9 NEC |
|
| 04/14/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |