Permit: T09BU00345

Parcel: 141387270

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09BU00345

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/23/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) NEED #8 INSULATED BOND WIRE INSIDE PLASTIC CONDUIT, FROM WET NICHE FIXTURE (POOL LIGHT)
2) NEED AN APPROVED J-BOX
3) POTTING COMPOUND TO COVER EXPOSED CU. WIRE INSIDE LIGHT FIXTURE
4) WILL GET INFORMATION REF. UNDERGROUND WIRING, IN ON OUT OF CONDUIT, 5' HORIZONTAL SPACE IS REQUIRED
5) WILL FIND OUT REF GFCI BREAKER, GFCI RECPT LOCATION IN CIRCUIT
6) WHAT IS PLAN FOR COMPLIANCE FOR VACUUM RELIEF ON MAIN DRAIN
04/23/2009 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL
2) COVER UNUSED SPACES AT SUB-PANEL