Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 06/23/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) NEED #8 INSULATED BOND WIRE INSIDE PLASTIC CONDUIT, FROM WET NICHE FIXTURE (POOL LIGHT) 2) NEED AN APPROVED J-BOX 3) POTTING COMPOUND TO COVER EXPOSED CU. WIRE INSIDE LIGHT FIXTURE 4) WILL GET INFORMATION REF. UNDERGROUND WIRING, IN ON OUT OF CONDUIT, 5' HORIZONTAL SPACE IS REQUIRED 5) WILL FIND OUT REF GFCI BREAKER, GFCI RECPT LOCATION IN CIRCUIT 6) WHAT IS PLAN FOR COMPLIANCE FOR VACUUM RELIEF ON MAIN DRAIN |
|
| 04/23/2009 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 2) COVER UNUSED SPACES AT SUB-PANEL |