Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU00342
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2009 | FIRE - ALARM FINAL | Partial Approval | 1.) The addition to the fire alarm system for the server room and computer room have ben approved. 2.) Complications with the existing fire alarm system in the school have been noted. a.) Activation of the pull ststions are not being recieved by central alarm. b.) One of the pull station activated was recieved as a water flow alarm. That portion of the building is not sprinklered. |