Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE WEATHERPROOF HOUSING AROUND REMOTE CONDENSOR |
|
| 03/24/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HOOD (TYPE 1) AND MAKE UP AIR NOT INTERLOCKED 2. MAKE UP AIR REGISTER BLOCKED OFF WITH PLASTIC BAG 3. ELEC. WIRING AT EXHAUST FANS NOT APPROVED FOR EXTERIOR APPLICATIONS 4. GREASE RECEPTORS ON ROOF NOT PROPERLY INSTALLED OR PIPED 5. GREASE DUMPING ON ROOF IS CAUSING HOLES IN ROOFING MATERIAL AND DAMAGE TO STRUCTURE 6. WATER HEATER FLUE VENT IS WITHIN 10' OF MAKE UP AIR INTAKE 7. PLASTIC BAG TAPED OVER WATER HEATER COMBUSTION AIR INTAKE 8. HOLES IN EXHAUST FAN MOTOR COMPARTMENT, THIS IS NOT A WET LOCATION ASSEMBLY 9. PROVIDE HINGE KIT FOR GREASE DUCT ACCESS |