Permit: T09BU00276

Parcel: 125081000


Addresses:

2419 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09BU00276

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/05/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
NO ONE AT SITE @ 8:45
02/27/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/26/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PERMITS FOR 2 REMOTE CONDENSING UNITS ON ROOF. UNITS NOT PROPERLY INSTALLED.
2. PROVIDE APPROVED ROOF JACKS FOR REMOTE CONDENSING UNITS
3. PROVIDE PERMIT FOR AC UNIT ON ROOF
4. AC UNIT NOT PROPERLY INSTALLED
5. PROVIDE HINGE KITS ON 3 EXHAUST FANS TO HOOD FOR CLEANING AND FURTHER INSPECTION
6. PROVIDE GREASE RECEPTORS ON ROOF
FOR 3 EXHAUST FANS
7. WASTE VENT TOO CLOSE TO MAKE UP AIR INLET

NOTE: DUCT SEALER ON AC UNIT STILL WET

8. PROVIDE INTERLOCK BETWEEN EXHAUST FANS
AND MAKE UP AIR