Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU00103
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2009 | FIRE - ALARM FINAL | Approved | ||
02/27/2009 | FIRE - ALARM FINAL | Denied | Not approved 2/27/09. Had to discontinue testing due to an electrical short on the Loop Circuit. Horns, storbes, smokes, loop circuit break already tested in the following locations; 1.) Section 1 ( as noted on TFD copy) Rooms 1, 2, and 3, restroom area and principals office. 2.) Section 2. Rooms 4, 5 and restroom area. 3.) Section 3. Rooms 7, 8, 9, 10, restroom areas. Learning Center, Library and Activity Center. The electrical short in the loop circuit was initiated in room 10 upon testing for a Ground fault detection. Unable to successfully get a Ground Fault detection on the loop up to this point in the test. |