Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09BU00003
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/12/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOBODY ON SITE |
|
01/13/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COOKING APPLIANCES MUST FIT UNDER HOOD OR BE REMOVED 2. PROVIDE PROPER INSTALLATION OF EXHAUST FAN ON ROOF (HINGE KIT) 3. PROVIDE PROPER INSTALLATION OF GREASE TROUGH ON ROOF 4. REPAIR OR REPLACE BROKEN ELECTRICAL CONDUIT TO EXHAUST FAN ON ROOF 5. PROVIDE APPROVED ELECTRICAL CONDUIT TO EXHAUST FAN (CORD NOT APPROVED METHOD) 6. INTERLOCK HOOD EXHAUST AND MAKE UP AIR |