Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2009 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 04/13/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOBODY HOME |
|
| 02/17/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A PAN IS NOT REQUIRED IN THE LOCATION OF THE WATER HEATER. IT IS OUTSIDE THE HOUSE AND THE T&P RELIEF WOULD DISCHARGE INTO THE GARAGE (AS IT DID BEFORE) BESIDES YOU LEFT THE PAN DRAIN OPEN, SO IF IT DID DISCHARGE INTO THE PAN IT WOULD STILL DRAIN INTO THE GARAGE. 2. YOU HAVE SCREWED THE VENT CONNECTOR INTO THE VENT, CUTTING OFF THE AIR FLOW BETWEEN THE VENT WALLS. THIS IS NOT NECESSARY. THE SCREWS ARE FOR THE VENT CONNECTOR ONLY, NOT THE VENT 3. YOU INSTALLED A PRESSURE RELIEF VALVE AT AN EXTERIOR HOSE BIB BUT LEFT FEMALE THREADS AT THE VALVES. IT MUST HAVE A PLAIN END. THERE IS NO AVB ON THE HOSE BIBB. 4. YOU DID NOT REPLACE THE UNAPPROVED GAS VALVE WITH AN AGA OR CSA APPROVED VALVE. THIS DOES NEED TO BE DONE. |