Permit: T08PL01785

Parcel: 130051900


Addresses:

2218 S NORRIS AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/24/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
10LB. TEST IS OK
LEFT GAS CARD
12/22/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOUR TEST GAUGE IS BROKEN
AND PIPING SHALL BE RIDGID INTO WATER HEATER ENCLOSURE. WITH APPROVED VALVE.
12/15/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THERE IS A NEW WATER HEATER & FURNACE INSTALLED WITHOUT PERMITS.

1. PROVIDE MINIMUM 10 PSI TEST ON ENTIRE GAS SYSTEM WITH TEST GAUGE IN 1/10 POUND INCREMENTS TO HOLD FOR MINIMUM 15 MINUTES WITH NO LOSS OF PRESSURE AT TIME OF INSPECTION
2. PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES
3. PROVIDE RIDGID NIPPLE THRU FURNACE APPLIANCE HOUSING.
4. PROVIDE WEATHERPROOF ENCLOSURE FOR NEW WATER HEATER
5. PROVIDE TEMPERATURE & PRESSURE RELIEF DRAIN
PIPE (COPPER OR CPVC PLASTIC OR GALVANIZED
FULL SIZE 3/4" PIPE TERMINATING DOWN 6" TO 24"
FROM FINISH GRADE.
6. SEAL THE COMBUSTION AIR OPENING IN THE DOOR OF FURNACE CLOSET
7. PROVIDE AIR TIGHT SEAL AROUND RETURN AIR INTAKE TO FURNACE
8. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION OF FURNACE.