Permit: T08PL01764

Parcel: 116060140

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/16/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. OK FOR GAS; BACKFILL PIPING W/CLEAN FILL
2. SECURE WH VENT WITH 3 SHEETMETAL
SCREWS @ EACH JOINT
3. PROVIDE MATERIALS APPROVED FOR USE WITH HOT WATER FOR TPR DRAIN AND TERMINATE WITHOUT THREADS
4. RECALL FOR INSPECTION
12/12/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- THE MIN. CODE STANDARDS REQUIRE THE FOLLOWING
- CORRECT VENT; VENT CONNECTOR IS NOT EVEN CONNECTED TO THE B-VENT.
- INSERT CONNECTOR INTO B-VENT FITTING
- T&P SHALL BE OF APPROVED MATERIALS; FULL SIZE & OPERATIONAL. REF. 2006 UNIFORM PLUMBING CODE
- ALSO, WRAP PIPE MACHINE CLAMPING VISE MARKS BELOW GRADE
12/11/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXTEND 1" TO FIRST BRANCH CONN.
(INSTALL A FULL SIZED TEE)
2. CORRECT WATER HEATER VENT AND TEMPERATURE AND PRESSURE RELIEF VALVE TERMINATIONS
3. WRAP ALL TOOL MARKS BELOW GRADE AND SHADE PIPING WITH CLEANFILL