Permit: T08PL01728

Parcel: 119222580


Addresses:

1899 W MERLIN RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/12/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/10/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST
12/09/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 12/3/08 BEFORE CALLING FOR INSPECTION
12/03/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED COUPLINGS FOR UNDERGROUND PIPING
2. PROVIDE PRIMER & TAPE ON ALL FITTING & TOOL MARKS
3. PROVIDE MIN. 10 PSI TEST ON ALL GAS PIPING
4. COMPLETE GAS PIPING & PROVIDE SHUT OFF AT HOUSE
5. PROVIDE NEW AGA VALVES AND FLEXES AT FURNACE
6. EXTEND FLUE VENT FOR FURNACE & WATER HEATER 3' ABOVE COOLER
7. LIST MAY NOT BE COMPLETE
12/02/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
NO ONE AT HOME UNABLE TO DO INSPECTION 8:30 AM