Permit: T08PL01723

Parcel: 138192390


Addresses:

354 W ELVIRA RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/24/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
02/18/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PVC IS NOT APPROVED MATERIAL FOR T&P RELIEF DRAIN (YOU MAY USE CPVC)
2. IF WATER HEATER VENT IS WITHIN 10 FEET OF EVAP. COOLER IT IS TO EXTEND TWO FEET ABOVE COOLER
3. FEMALE PLASTIC THREADS NOT APPROVED WITH MALE METALLIC THREADS
02/11/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PROVIDE ROOF JACK FOR GAS PIPING THRU ROOF ON WEST SIDE WATER HEATER
2. PROVIDE 1" CLEAR AROUND AND APPROVED FLUE VENT AND CAPS FOR EAST AND WEST SIDE WATER HEATERS
3. RUN T&P DOWN 6" TO 24" FROM GROUND
4. PROVIDE NEW PRESSURE TEST
5. EXTEND 2' ABOVE FURNACE