| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. OWNER TO CHANGE VENT CONNECTOR TO B VENT 2. HARD PIPE TO INSIDE ENCLOSURE THEN INSTALL VALVE & FLEX 3. THE REST OF THE CORRECTIONS MADE OK 4. OK FOR GAS UCC LEFT AT METER |
|
| 01/30/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO INSTALL SEDIMENT TRAP AT WATER HEATER |
|
| 01/07/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - NEW WATER HEATER REQUIRES PROPER VENTING, TPR TERMINATIONS, GAS AND WATER CONNECTIONS, SEDIMENT TRAP AND PIPING. - INSTALL DRAFT COLLAR AT VENT CONNECTOR - PROVIDE TYPE B VENT ABOVE ENCLOSURE AND TERMINATE 1' ABOVE ROOF - GAS FLEX MAY NOT PENETRATE ENCLOSURE; HARD PIPE, SUPPORT AND SECURE PIPING W/APPROVED PIPE CLAMPS - BLACK IRON MAY NOT BE USED FOR WATER - HOSE BIBS REQUIRE VACUUM BREAKERS |
|
| 12/01/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE BESIDES THE LIST FROM 11/26/08 YOU WILL NEED AN APPROVED MOBILE HOME CONNECTOR AND VALVE. |
|
| 11/26/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED GAS VALVES FOR ALL APPLIANCES 2) COMPLETE PIPING TO WH AND INSTALLATION OF WATER HEATER 3) SUPPORT AND SECURE GAS PIPING UNDER ? AND CLOSE TO OUTLETS AND INLET 4) TEST TO 10 PSI WITH A 15 PSI GAUGE. CODE REQUIRES 1/10TH PSI INTREMENTATION |