Permit: T08PL01705

Parcel: 10607022A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/18/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1. OWNER TO CHANGE VENT CONNECTOR TO B VENT
2. HARD PIPE TO INSIDE ENCLOSURE THEN
INSTALL VALVE & FLEX
3. THE REST OF THE CORRECTIONS MADE OK
4. OK FOR GAS UCC LEFT AT METER
01/30/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED TO INSTALL SEDIMENT TRAP AT WATER HEATER
01/07/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NEW WATER HEATER REQUIRES PROPER VENTING, TPR TERMINATIONS, GAS AND WATER CONNECTIONS, SEDIMENT TRAP AND PIPING.
- INSTALL DRAFT COLLAR AT VENT CONNECTOR
- PROVIDE TYPE B VENT ABOVE ENCLOSURE AND
TERMINATE 1' ABOVE ROOF
- GAS FLEX MAY NOT PENETRATE ENCLOSURE; HARD PIPE, SUPPORT AND SECURE PIPING W/APPROVED PIPE CLAMPS
- BLACK IRON MAY NOT BE USED FOR WATER
- HOSE BIBS REQUIRE VACUUM BREAKERS
12/01/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE BESIDES THE LIST FROM 11/26/08 YOU WILL NEED AN APPROVED MOBILE HOME CONNECTOR AND VALVE.
11/26/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED GAS VALVES FOR ALL APPLIANCES
2) COMPLETE PIPING TO WH AND INSTALLATION OF WATER HEATER
3) SUPPORT AND SECURE GAS PIPING UNDER ? AND CLOSE TO OUTLETS AND INLET
4) TEST TO 10 PSI WITH A 15 PSI GAUGE. CODE REQUIRES 1/10TH PSI INTREMENTATION