Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/21/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE EXCESS FLUX FROM SOLDIER JOINTS 2. INSTALL VACUUM BREAKERS ON ALL HOSE BIBS 3. REPLACE ALL POLYBUTYLENE TUBING INCLUDING FIXTURE SUPPLIES 4. ISOLATE TUBING RUBBING AGAINST GANG NAIL STRIPS 5. SECURE TUBING OVERHEAD PER PEX MANUFACTURES INSTALLATION INSTRUCTIONS 6. HAVE INSTALLATION INSTRUCTION BOOKLET OR UPC CODE BOOK ON SITE FOR INSP. 7. INSPECTION STOPPED |
|
| 11/20/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE 18" OF COPPER ON WATER HEATER PIPING AND WATER SOFTENER 2. PROVIDE MEANS FOR WATER HAMMER AT WASHER 3. PROVIDE NEW SUPPLIES FOR ALL WATER SUPPLY TO FIXTURES 4. PROVIDE SUPPORT ON OVERHEAD WATER PIPING 1. INSIDE WALLS OK TO COVER |