Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2009 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 07/09/2009 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) SINGLE WALL VENT CONNECTOR MAY NOT PENETRATE CEILING SPACE AND REQUIRES 6" OF CLEARANCE FROM COMBUSTIBLES 2) B-VENT MAY NOT CHANGE BACK TO SINGLE WALL 3) B-VENT SHALL BE INSTALLED IN CORRECT DIRECTION OF FLOW 4) WOOD WH STAND DOES NOT COMPLY WITH IBC BLDG CODES 2301.2 AND 2305.1.2.1 5) PROVIDE A LISTED APPROVED STAND, SET WH ON FLOOR OR BUILD TO IBC CODES 6) IF WOOD IS USED INSTALL A PAN UNDER HEATER 7) CAP FUTURE ? AND PROVIDE TEST 8) INSTALL GAUGE AT METER LOCATION 9) GROUNDING IS NOT ELECTRICAL BONDING 10) YOU MAY BOND WATER TO GAS OR BOND TO PANEL 11) CONTINUED DENIED INSPECTIONS MAY RESULT IN RE-INSPECTION FEE |
|
| 07/06/2009 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) CALLED 747-0423 NUMBER NOT WORKING 2) NO ONE AT HOME UNABLE TO DO INSPECTION |
|
| 05/08/2009 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/01/2009 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |