Permit: T08PL01668

Parcel: 14111002B


Addresses:

8300 E VALENCIA RD


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T08PL01668

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2010 SITE - SEWER Approved IVRS - Inspection :*
08/05/2010 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
02/11/2010 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
1. NEED AUTHORIZATION TO DISCHARGE FROM PC DEQ
2. WOOD TERMINATION OR TRACER WIRES IN MANHOLES WITH CORRECT TERMINATION OF MANHOLE COVERS TO PIMA COUNTY & CITY OF TUCSON STANDARDS
02/19/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
VACUUM TEST MANHOLE #12, 13, 14 OK
02/18/2009 SITE - SEWER Partial Approval IVRS - Inspection :*
AIR TESTING FROM MANHOLE:
#11 TO #12 8" SDR 35 PIPING OK
#12 TO #13 OK 8" SDR 35 PIPING OK
#12 TO #14 OK 8" SDR 35 PIPING OK

MANDRILL FROM MANHOLE #11 TO 12 OK; 12 TO 13 OK;
12 TO 14 OK

MIRROR OF SAME OK
12/30/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
1) BEDDING, LAYING SHADING, TRAILER 8 SDR 35 FROM MANHOLE #12 TO 14. BASES POURED MANHOLE #12, 13 & 14
12/23/2008 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
12/19/2008 SITE - SEWER Partial Approval IVRS - Inspection :*
BEDDING, LAYING, TRACER FROM EXISTING
MANHOLE #11 8" SDR35 TO NEW MANHOLE #12,
TO NEW MANHOLE #13 TESTING AT LATER DATE