Permit: T08PL01636

Parcel: 115201480


Addresses:

1919 W LINDEN ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/16/2008 PLUMBING - GAS PRESSURE TEST Approved
12/02/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
11/25/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
VALVE GOES AHEAD OF UNION AT HSE. RETEST.
OK TO COVER YARD
RELIEF VALVE TERMINATION IS VERTICAL W/OUT THREADS.
PROVIDE PETITION OF APPEAL FOR WH TPR DRAIN INTO PAN
PROVIDE PERMIT FOR ELECTRICAL WIRING TO WH
11/17/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. REPAIR OF GAS LINE
2. BLACK PIPE NOT PERMITTED BELOW GRADE
3. TAPING IS LIMITED TO FITTINGS AND SHORT
SECTIONS STRIPPED FOR THREADINGER MARRED BY WRENCHES
4. GAS FIRED WATER HEATER REMOVED AND ELECTRIC WATER HEATER INSTALLED WITHOUT PERMITS
T&P RELIEF DRAIN NOT APPROVED
NOT ON APPROVED BASE
CONNECTION TO ELECTRIC NOT APPROVED
WILL NEED: AN ELECTRICAL INSPECTOR TO INSPECT ELECTRIC WIRING RUN TO WATER HEATER
5. REMOVE AND CAP OFF GAS WATER HEATER VENT
6. GAS LINE TO HAVE TEN POUNDS PRESSURE ON SYSTEM WHEN INSPECTOR ARRIVES.

1/2 OVERLAP DOUBLE WRAPPED TO 40 MIL. USE TAPE PRIMER