Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2009 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 01/12/2009 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* TEST IS OK |
|
| 01/06/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* MAKE REPAIR TO GAS SYSTEM AT PIPING FROM EXISTING VALVE FOR BBQ & FIREPLACE GAS LINE AND PROVIDE A 10 PSI TEST ON THIS SECTION WITH TEST GAUGE IN 1/10 POUND INCREMENTS AT TIME OF FUTURE INSPECTION. PRIME THEN TAPE TOOL MARKS AND FITTINGS UNDERGROUND AT THAT LOCATION. LEFT-RIGHT NIPPLE AND COUPLING FOR PIPING TIE TOGETHER. GAS IS ON TO REST OF SYSTEM CURRENTLY |