Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 11/13/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. NO ACCESS INSIDE HOUSE 2. REMOVE ALL FOIL TAPE FROM WATER HEATER VENT 3. DO NOT COUPLE 2 PIECES OF DOUBLE WALL VENT PIPE WITH A PIECE OF SINGLE WALL 4. USE SIMPLE WALL PIPE FROM THE WATER HEATER DRAFT DIVERTOR UP INTO EXISTING DOUBLE WALL PIPE 5. PROVIDE 3 SCREWS IN EACH JOINT AND NO TAPE 6. RESCHEDULE WHEN SOMEONE WILL BE HERE |
|
| 11/12/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO COVER YARD COMPLETE WH VENTING CORRECT T&P INSTALL SEDIMENT TRAP |