Permit: T08PL01567

Parcel: 107031020


Addresses:

2555 N JORDAN DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/25/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
11/19/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
GAS CARD AT METER

SEE NOTE #6 & CONTINUE DOUBLE WALL TO CAP ON WATER HEATER AND EXTEND FURNACE VENT UP WITH DOUBLE WALL VENT PIPING PER NOTE #6 ABOVE.
10/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED COUPLING ON UNDERGROUND PIPING
2. TEST TO BE IN PLACE MINIMUM 10 PSI FOR 15 MINUTES
WITH NO LOSS OF PRESSURE AT TIME OF INSPECTION
GAUGE 1/10 POUND INCREMENTS
3. PRIME THEN TAPE ALL FITTINGS & TOOL MARKS ON
ALL BELOW GROUND PIPING. DOUBLE WRAP TAPE TO
ACHIEVE 40 MIL. THICKNESS
4. VENT FROM WATER HEATER TO BE MADE UP CORRECTLY AND JOINTS TO BE SECURED WITH GALV SCREWS
5. T&P REQUIRES DRAIN PIPING
6. PROVIDE DOUBLE WALL VENT PIPING THRU CEILING ROOF STRUCTURE TO 3' ABOVE TOP OF COOLER WHEN WITHIN TEN FEET OF COOLER INTAKE WITH APPROVED CAP FOR BOTH WATER HEATER & FURNACE
7. PROVIDE APPROVED GAS SHUT OFF VALVES AT FURNACE AND WATER HEATER
8. PROVIDE GASKETED SELF-CLOSING DOOR TO WATER HEATER