Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T08PL01561
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
11/10/2008 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE APPROVED COUPLING 2. PROVIDE 18" OF COVER PER CODE AND 12" MIN. 3. PROVIDE TEST ON ALL GAS PIPING 4. PROVIDE PRIMER AND TAPE ON ALL TOOL MARKS AND FITTINGS 5. PROVIDE AGA VALVES AND FLEXES 6. PROVIDE SUPPORT ON ALL GAS PIPING |
|