Permit: T08PL01554

Parcel: 130160270


Addresses:

4401 E 28TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/29/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
OWNER HAS A/C UNIT -- COOLER IS REMOVED
GAS CARD AT METER S.W. GAS 889-1888
10/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. VENT FROM WATER HEATER AND FURNACE TO BE MADE UP CORRECTLY AT SINGLE TO DOUBLE WALL CONNECTION, REMOVE ALL TAPE PROVIDE FASTENERS AT EACH JOINT OF VENT PIPING
2. EXTEND DOUBLE WALL ON ROOF FULL SIZE TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH APPROVED VENT PIPING
3. TEMPERATURE & PRESSURE RELIEF IS LEAKING AND MUST BE FUNCTIONAL
4. CAP OLD GAS PIPING SYSTEM