Permit: T08PL01329

Parcel: 118200750


Addresses:

1480 S 10TH AV


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T08PL01329

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/23/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. GAS LINE REPAIR NOT MADE OK. TAPE ALREADY COMING OFF. WILL REQUIRE AN APPROVED TAPE PRIMER TO BE USED ON TAPED JOINTS. TAPED PIPE IS LIMITED TO FITTINGS AND PIPING MARRED BY WRENCHES. TAPING TO BE SPIRALLY WRAPPED HALF OVERLAP DOUBLE WRAP OF MINIMUM 10 MIL. TAPE TO PROVIDE MINIMUM 40 MIL. THICKNESS.
PRIMER REQUIRED. SEE INSTALLATION STD. 2006 UPC.
2. ALSO, OUTDATED VALVES WERE REPLACED WITH APPROVED VALVES. FURNACES WILL REQUIRE A SEDIMENT TRAP AND PER MANUFACTURES SPEC's. FLEX CONNECTORS MAY NOT BE REUSED
3. CONTINUED "NOT READY" WILL RESULT IN
REINSPECTION FEE
09/19/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*